6 Specifications

6.2 Specific rated operational data

6.2 Specific rated operational data
6.2.1 DA1-12... series
Size
Rated operational current
Overload current for 60 s every 600 s
Apparent power at rated operation
Rated motor output
Power input side (primary side):
Number of phases
Rated voltage
Input current (phase current)
Minimum braking resistor
Switching frequency (pulse frequency)
Factory default setting
Settings range
Maximum leakage current to earth (PE), without
motor
Efficiency
Heat dissipation at I
e
Frame size
148
Symbol
I
e
I
L
1)
230 V
S
240 V
S
230 V
P
230 V
P
U
LN
I
LN
R
B
f
PWM
f
PWM
I
PE
η
P
V
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Unit
4D3
7D0
A
4.3
7.0
A
6.45
10.5
kVA
1.71
2.79
kVA
1.79
2.91
kW
0.75
1.5
HP
1
2
single-phase or two-phase
V
200 - 10 % - 240 + 10 %, 50/60 Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
A
8.5
15.2
Ω
100
50
kHz
16
16
kHz
4 - 32
4 - 32
mA
2.49
2.49
0.94
0.96
W
45.75
63
FS2
FS2
011
10.5
15.75
4.18
4.36
2.2
3
19.5
35
16
4 - 32
2.49
0.95
103.4
FS2