3 Installation
3.6 Electrical Installation
3.6.2.3 STO terminals
3.6.2.4 Connection example
114
1 2 3 4 5 6 7 8 9 10 11 12 13
Figure 81: STO control signal terminals (direct enable)
Control signal terminal 12 (STO+) must always be connected to
+24 V and control signal terminal 13 (STO-) must always be
connected to 0 V (reference point for +24 V)!
Without the connection of a power supply (24 V DC) to control signal
terminals 12 and 13, the control section and the inverter will remain blocked.
An Inhibt (Inhibit = block) message is displayed.
The control cables should be screened and twisted. The screen is applied on
one side in the proximity of the variable frequency drive (PES).
+24 V DI1
DI2
+10 V AI1
1
2
5
6
3
4K7
M
M
FWD
REV
R1
Figure 82: Simple connection example
Prevent the shielding from unbraiding, i.e. by pushing the
separate plastic covering over the end of the screen or by
pushing a rubber grommet on the end of the screen.
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
0 V STO+ STO-
12
13
7
PES
PE
PES
ZB4-102-KS1
STO+ STO-
12
2
1
OFF
3
2
Cu 2.5 mm
M4
STOP
13
Motor Stop