Function Explanations

00
Not Used: All unused output terminals of the AC drive should be set to 00.
01
Drive Ready: The output terminal will be active when the drive has no faults
and is ready to run.
02
Drive Running: The output terminal will be active when the drive is
generating an output from the T1, T2, T3 terminals.
03
Fault Indication: The output terminal will be activated when faults occur.
04: Warning: The output terminal will be active when there is a fault with
communication or PID feedback.
05
At Speed: The output terminal will be active when the drive output
frequency reaches the value set by your command source.
06
F
< F
during run: The output terminal will be active when the drive's U,
out
min
V, W terminals are generating no output.
07
Desired Frequency Attained (40.07): The output terminal will be active when
the output frequency is above the desired frequency.
08
Below Desired Frequency (40.07): The output terminal will be active when
the output frequency is below the desired frequency.
09
PID Supervision
10
Over Voltage Warning: The output terminal will be active when output
voltage of the drive exceeds 90% of the maximum voltage limit.
11
Over Heat Warning: The output terminal will be active when temperature of
the drive exceeds 90% of the maximum heat limit.
12
Over Current Stall Warning: The output terminal is active when the over
current stall function is enabled.
13
Over Voltage Stall Warning: The output terminal will be active when the over
voltage stall function is enabled.
14
Final Count Value: The output terminal will be active when the count reaches
the setting in 30.29.
15
Midpoint Count Value: The output terminal will be active when the count
reaches the setting in 30.30.
16
Reverse direction command: The output terminal will be active when the
drive is in reverse.
17
Under Current detection: The output terminal will be active when the output
current is under 70.11 and the time has exceeded 70.13.
5-26