3.6.2.2 Connection data and functions
Terminal
1
+24 V
2
DI1
3
DI2
4
DI3
5
+10 V
6
AI1
DI4
7
0 V
8
AO1
DO1
9
0 V
10
DI5
AI2
11
AO2
DO2
12
STO+
13
STO-
14
K11
15
K14
16
K12
17
K23
18
K24
1) Configurable function: Manual MN04020006Z-EN describes the functions and modes for the configurable control signal terminals.
The functions that are set ex-factory and the electrical connection data of the
control signal terminals are listed in the following table.
Table 16: Factory-set functions of the control terminals
Signal
Control voltage for DI1 - DI5,
output (+24 V)
Digital Input 1
Digital Input 2
Digital Input 3
Reference voltage,
Output (+10 V)
Analog Input 1
Digital Input 4
Reference potential
Analog output 1
Digital output 1
Reference potential
Digital Input 5
Analog Input 2
Analog output 2
Digital output 2
Safe Torque Off +
Safe Torque Off -
Relay 1, changeover contact
Relay 1, N/O (changeover
contact)
Relay 1, N/C (changeover
contact)
Relay 2, N/O
Relay 2, N/O
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Description
Maximum load 100 mA,
Reference potential 0 V
8 - +30 V (High, R
> 6 kΩ)
i
8 - +30 V (High, R
> 6 kΩ)
i
8 - +30 V (High, R
> 6 kΩ)
i
maximum load 10 mA
Reference potential 0 V
• Analog: 0 - +10 V (R
> 72 kΩ)
i
0/4 - 20 mA (R
= 500 Ω)
B
switchable using parameter P2-30
• digital: 8 - 30 V (High)
0 V = connection terminal 9
• Analog: 0 - +10 V
maximum 20 mA
switchable via parameter P2-11
• digital: 0 - +24 V
0 V = connection terminal 7
• digital: 8 - 30 V (High)
• Analog: 0 - +10 V (R
> 72 kΩ)
i
0/4 - 20 mA (R
= 500 Ω)
B
switchable using parameter P2-33
• Analog: 0 - +10 V
maximum 20 mA
switchable via parameter P2-13
• digital: 0 - +24 V
Enable = +24 V
Enable = 0 V
Maximum switching load:
250 V AC/6 A or 30 V DC/5 A
Maximum switching load:
250 V AC/6 A or 30 V DC/5 A
Maximum switching load:
250 V AC/6 A or 30 V DC/5 A
3 Installation
3.6 Electrical Installation
Default settings
(= Input for external control voltage,
+24 V DC, reference potential at terminal 7
or terminal 9)
FWD (clockwise rotating field enable)
REV (anticlockwise rotating field enable)
Select AI1 REF/f-Fix
(Switch-over of the setpoint source from
Analog input 1 to fixed frequency)
Select f-Fix Bit0
(Selection of the frequency setpoint values
of Bit0: f-Fix1 = 5 Hz (P2-01))
Output frequency f-Out
(P2-11 = 8, ADO1 function & mode)
Select f-Fix Bit0
Output current A-Out
(P2-13 = 9, ADO2 function & mode)
→ section 2.10, "STO function", page 68
(common connection for N/C and N/O)
Closed = No error message
Closed = No 24 V control voltage or error
message (Error)
Closed = RUN operating signal
113