Specifications
Motor feeder
Output voltage
DA1-12..., DA1-32..., DA1-34..., DA1-35...
rated motor power
at 230 V, 50 Hz
at 400 V, 50 Hz
at 500 V, 60 Hz
Output frequency
Range, parameterizable
Resolution
Rated operating current
Overload current for 60 s every 600 s
Starting current for 4 s every 40 s
Motor cable length
screened
unscreened
with motor choke
Switching frequency (pulse frequency)
Operating mode
SLV, max. Speed error
DC-braking
Time before starting
Motor pick-up control function
Brake chopper
Braking current during continuous operation
Maximum braking current
DA1 Variable Frequency Drives 08/18 MN04020005Z-EN www.eaton.com
Symbol
Unit
Value
U
V
3~ 0 - U
2
P
kW
0.75 - 75
P
kW
0.75 - 250
P
kW
0.75 - 110
f
Hz
0 - 50/60 (max. 500 Hz)
2
Δf
Hz
0.1
I
A
IP20: 4.3 - 72 / 370 - 450
e
IP55: 24 -302
IP66: 4.3 -18
I
%
150
L
I
%
200
L
l
m
100
l
m
150
Δl
%
100 (increased maximum cable length)
f
kHz
4 - 32 (double modulation) / 2 - 16 (effective)
PWM
Maximum value depends on rating
V/Hz control, slip compensation, vector control
Δn
%
±0.5
t
s
0 - 25, in the event of a stop
Yes
Yes
I
%
100 (I
BR
I
%
150 for 60 s
BRmax
6 Specifications
6.1 General rating data
e
)
e
145