PowerXL DG1 Series VFD Installation Manual Effective March 2014 New Information...
Page 3
OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential...
Page 4
Support Services Support Services The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need. Whether it is by phone, fax, or email, you can access Eaton’s support information 24 hours a day, seven days a week.
Never touch live parts or cable connections of the ● adjustable frequency drive after it has been disconnected from the power supply. Due to the charge in the capacitors, these parts may still be live after disconnection. Fit appropriate warning signs PowerXL DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
DC link/brake resistor terminals (DC–, DC+/R+, R–) are live when the drive is connected to power, even if the motor is not running. Contact with this voltage is extremely dangerous and may cause death or severe injury. viii PowerXL DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Page 11
A hard copy of this protection in case of direct or indirect contact, only an information may be ordered from Eaton literature RCD or RCM of Type B is allowed on the supply side of fulfillment.
Page 12
Any electrical or mechanical modification to this drive without the same cross-sectional area as the original protective prior written consent of Eaton will void all warranties and may earthing conductor must be connected, or the cross-section result in a safety hazard in addition and voiding of the UL ®...
DC capacitors (i.e. power-ups by applying power) is five in terminals (U, V, W) to avoid damaging the drive during motor ten minutes. or cable testing. PowerXL DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Page 14
AC source. Failure to follow these instructions can result in injury and/or equipment damage. For more technical information, contact the factory or your local Eaton sales representative. PowerXL DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
2-wire connector to the receptacle on the control board. necessary to install, set and customize parameters, start up, troubleshoot and maintain the Eaton DG1 Series adjustable Figure 1. RTC Battery Connection frequency drive (AFD). To provide for safe installation and...
Motor protection; thermistor (can be connected to drive directly) Cable lengths, motor cables, shielding (EMC) Motor and application, parallel operation of multiple motors on a VFD, bypass circuit, DC braking PE L1 L2 L3 PE U DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
EMC and low voltage regulations. Good grounding measures are a prerequisite for the effective insert of further measures such as shielding of filters. Without respective grounding measures, further steps are superfluous. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
On a variable frequency drive, the total harmonic distortion is around 120%. To assist in the calculation of system harmonics, a Harmonic Estimation Calculator Tool is available at www.eaton.com/drives. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
AC network into a DC voltage. This DC voltage is used to generate a three-phase AC voltage with adjustable frequency and assigned amplitude values for the variable speed control of three-phase asynchronous motors. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
DG1-32: 0.55 kW to 75 kW (230V, 50 Hz) or 0.75 hp to 100 hp (240V, 60 Hz) DG1-34: 0.75 kW to 150 kW (400V, 50 Hz) or 1 hp to 200 hp (460V, 60 Hz) DC link—chokes, to minimize current harmonics DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
The parallel connection of multiple motors in the output of the frequency inverter is only permitted with V/Hz characteristic curve control. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Storage Information concerning the guarantee can be found in the Eaton General Terms and Conditions of Sale. If the frequency inverter is stored before use, suitable ambient conditions must be ensured at the site of storage: Storage temperature: –40°F to 158°F (–40°C to 70°C) ●...
Use 75°C copper wire only ● Use UL listed conduit fittings with the same type rating ● (Type 1/Type 12) as the enclosure See Appendix D—Safety Instructions for UL and cUL for details. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Residual current circuit breakers must be suitable for: the protection of installations with DC current component ● in case of fault scenario (RCD type B) high leakage currents ● brief discharges of pulse current spikes ● DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
DG1 frequency inverters are ideal for use in commercial networks (1st environment). Table 14. Maximum Motor Cable Length by Frame Size without dV/dT Protected C2 Ratings Frame Size Maximum Cable Length (m) Category C3/C4 DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Selecting the motor contactor is done according to the rated operational current of the motor to be connected. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
The pull-out torque remains at the same level as in input inverter’s output can lead to nuisance tripping. operation with 50 Hz. The heat class of the motor must be at least F in 87 Hz operation. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
2474 min Motor frequency 50 Hz 50 Hz 87 Hz Notes Star connection: 400V, 50 Hz. Delta connection: 230V, 50 Hz. Delta connection: 400V, 87 Hz. Note the permitted limit values of the motor. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
I > I > I > apparatus for EX areas. L1 L2 L3 U V W Table 16. Bypass Motor Control Item No. Description Input/bypass contactor Output contactor DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
After disconnecting the supply, wait at least five minutes before removing the cover to allow the intermediate circuit capacitors to discharge. Pay attention to hazard warnings! DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Minimum clearances A and B for drives with Type 12 (IP54) enclosure is 0 mm (in). kW ratings are at 400V / 50 Hz. The above guidelines apply unless testing has been completed to validate a design outside of these recommendations. FR6 and 575 Vac available in 2015. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
(refer to the drive mounting template printed on the outside carton). Screw: Four M5x15 or 3/16 inch Nut: Four M5 Screw: Four M5x15 or 3/16 inch or 3/16 inch Nut: Four M5 or 3/16 inch DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Page 41
(refer to the drive mounting template printed on the outside carton). Screw: Four M6x15 or 1/4 inch Nut: Four M6 or 1/4 inch Screw: Four M8x15 or 3/8 inch Nut: Four M8 or 3/8 inch DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Page 42
Step 2: Remove the four screws (used to fix the drive to the Screw: Four M8x20 pallet) with an M8 or 3/8 inch wrench. or 3/8 inch Nut: Four M8 or 3/8 inch Step 3: Use a hook to lift the drive. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Use Class T (UL and cUL/CSA ® ) or type gG/gL (IEC 60269-1). Refer to Appendix B for proper fuse size selection. Consult with Eaton Electrical for further information on fusing requirements. Notes C1 protection requires external filtering. Consult factory.
Avoid running motor cables alongside or parallel to any other wiring. If it is necessary to run motor cables with other wiring, then maintain spacing between motor cables and other wiring in accordance with the table on Page 30. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Page 45
Ground strap mounting screws for wiring, the enclosure openings provided for conduit ● connections in the field shall be closed by UL listed conduit fittings with the same type rating (Type 1/ Type 12) as the enclosure. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Step 6: Fasten the rubber grommet and cable with a self-locking cable tie. Step 3: Cut the rubber grommet at the selected diameter. ≤ ≤ D1 + 2 mm Self-Locking Cable Ties Step 4: Run the cable through the rubber grommet. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Note: For ease of access, the board terminals blocks can be unplugged for wiring. Wire control to the control board. Note: Drive default is programmed for external interlock. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Relay output 3 shows VFD is at Ref. Frequency R2NC Relay 2 Normally Closed Fault Relay output 2 shows VFD is in a fault state R2CM Relay 2 Common R2NO Relay 2 Normally Open DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Programmable relay outputs: 2 x Form C (Relay 1 and Relay 2) and 1 x Form A (Relay 3), Relay 3 can be used as thermistor output Switching capacity: 24 Vdc/6A, 48 Vdc/2A, 240 Vac/6A, 125 Vdc/0.4A DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Control I/O terminals must be tightened to 4.5 in-lb (0.5 Nm) ● Control wiring shall be shielded twisted pairs to meet ● Wiring or ferrule size: 28~12 (Sol) AWG, 30~12 (Str) AWG, ● EMC levels required by IEC/EN 61800-3 (2004) or 0.2~2.5 mm DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
U, V, W: Connection terminals for the three-phase line to ● the AC motor (output, frequency inverter) PE: Connection for protective ground (reference potential). ● PES with mounted cable routing plate for shielded cables DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
DG1 delivery (see Figure 26) and note the date. Unless already done, attach the sticker close to the name plate of the AC drive. Product Modified Sticker Figure 26. Product Modified Sticker DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Avoid using painted surfaces (anodized, chromized). An grounded on one end, in the immediate vicinity of the supply overview of all EMC measures is provided in the figure on voltage source (PES). Page 41. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Connect the cable shielding in the output of the frequency inverter with a large surface area contact to the ground potential (PES). Large-area cable shield contacts with motor. Large-area earth connection of all metallic parts. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Symmetrical power cable with compact low-impedance shield. Recommended cable transfer impedance of 1–30 MHz max. See figure below. Screened cable equipped with compact low-impedance shield Figure 28. Cable Description PE Conductor and Shield PE Conductor Shield DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Remove the main cover of the AC drive (see Figure 30) and locate the screw jumper connecting the built-in RFI-filters to ground. Remove the screw jumper to disconnect the EMC protection. Once the screw is removed, it can be reconnected to re-engage the EMC protection. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
3280 ft (1000 m); max. 9842 ft (3000 m) (2000 m for corner grounded earth main systems) Vibration: 5–150 Hz EN 61800-5-1 Displacement amplitude: 1 mm (peak) at 5 Hz to 15.8 Hz (FR1–FR5) ● EN 60668-2-6 Maximum acceleration amplitude: 1g at 15.8 Hz to 150 Hz (FR1–FR5) ● DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Page 59
Motor overload protection Motor stall protection Motor underload protection DC bus overvoltage control Short-circuit protection of 24V reference voltages Surge protection Yes (differential mode 2 kV; common mode 4 kV) Common coated boards Yes (prevents corrosion) DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL508C Table 6.4. If power cubes or bypass are used, a UL recognized Class T fuse is recommended. Available in 2015. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Earthing conductor size is determined by the cross–sectional area of phase conductors according to IEC/EN61800–5–1:2007 Table 5. So if phase conductor size is changed, earthing conductor size should also be changed accordingly. If power cubes or bypass are used, a Class gG/gL fuse is recommended. Available in 2015. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL508C Table 6.4. If power cubes or bypass are used, a UL recognized Class T fuse is recommended. Available in 2015. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
Earthing conductor size is determined by the cross–sectional area of phase conductors according to IEC/EN61800–5–1:2007 Table 5. So if phase conductor size is changed, earthing conductor size should also be changed accordingly. If power cubes or bypass are used, a Class gG/gL fuse is recommended. Available in 2015. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
IP21/IP54 Metric and Type 1/12 UL REMOTE RUN FAULT BACK LOCAL RESET REMOTE STOP START 3.15 3.15 (80.0) (80.0) D 7.87 (200.0) Note: With flange kit installed, the bottom wiring box should be removed. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...
6 AWG– All models Control terminal 28~12 (Sol) AWG 250 kcmil block 30~12 (Str) AWG DG1-34170xx-xxxx 4 AWG– 250 kcmil Note The line and motor wire size for DG1-32088xx-xxxx can only be 1/0 AWG. DG1 Series VFD MN040002EN—March 2014 www.eaton.com...