Parameter Descriptions
5-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0 %
[0 - 100
Set the output frequency transferred to the
*
%]
output terminal X30/6 when the terminal is
configured as [45] Bus ctrl. in 5-66 Terminal
X30/6 Pulse Output Variable.
5-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0 %
[0 -
Set the output frequency transferred to the
*
100 %]
output terminal X30/6 when the terminal is
configured as [48] Bus Ctrl Timeout in
5-66 Terminal X30/6 Pulse Output Variable. And a
time-out is detected.
®
VLT
AutomationDrive FC 301/302 Programming Guide
MG33MH02 - Rev. 2013-09-30