Parameter Descriptions
16-71 Relay Output [bin]
Range:
0
[0 - 511 ]
*
3
3
16-72 Counter A
Range:
0
[-2147483648
*
- 2147483647 ]
16-73 Counter B
Range:
0
[-2147483648
*
- 2147483647 ]
16-74 Prec. Stop Counter
Range:
0
[0 - 2147483647 ] Returns the actual counter value of
*
16-75 Analog In X30/11
Range:
0
[-20 - 20 ] View the actual value at input X30/11 of MCB
*
16-76 Analog In X30/12
Range:
0
[-20 - 20 ] View the actual value at input X30/12 of MCB
*
150
VLT
Function:
View the settings of all relays.
Illustration 3.62 Relay Settings
Function:
View the present value of Counter A.
Counters are useful as comparator operands,
see 13-10 Comparator Operand.
The value can be reset or changed either via
digital inputs (parameter group 5-1* Digital
Inputs) or by using an SLC action (13-52 SL
Controller Action).
Function:
View the present value of Counter B.
Counters are useful as comparator operands
(13-10 Comparator Operand).
The value can be reset or changed either via
digital inputs (parameter group 5-1* Digital
Inputs) or by using an SLC action (13-52 SL
Controller Action).
Function:
precise counter (1-84 Precise Stop Counter
Value).
Function:
101.
Function:
101.
®
AutomationDrive FC 301/302 Programming Guide
16-77 Analog Out X30/8 [mA]
Range:
0
[0 - 30 ]
*
16-78 Analog Out X45/1 [mA]
Range:
0
[0 - 30 ] View the actual value at output X45/1. The value
*
16-79 Analog Out X45/3 [mA]
Range:
0
[0 - 30 ] View the actual value at output X45/3. The value
*
3.17.7 16-8* Fieldbus & FC Port
Parameters for reporting the BUS references and control
words.
16-80 Fieldbus CTW 1
Range:
0
[0 -
*
65535 ]
16-82 Fieldbus REF 1
Range:
0
[-200 -
*
200 ]
16-84 Comm. Option STW
Range:
0
[0 - 65535 ] View the extended fieldbus comm. option
*
16-85 FC Port CTW 1
Range:
0
[0 -
*
65535 ]
MG33MH02 - Rev. 2013-09-30
Function:
View the actual value at input X30/8 in mA.
Function:
shown reflects the selection in 6-70 Terminal X45/1
Output.
Function:
shown reflects the selection in 6-80 Terminal X45/3
Output.
Function:
View the two-byte control word (CTW) received
from the Bus-Master. Interpretation of the
control word depends on the fieldbus option
installed and the control word profile selected in
8-10 Control Profile.
For more information, refer to the relevant
fieldbus manual.
Function:
View the two-byte word sent with the control
word from the Bus-Master to set the reference
value.
For more information, refer to the relevant
fieldbus manual.
Function:
status word.
For more information, refer to the relevant
fieldbus manual.
Function:
View the two-byte control word (CTW) received
from the Bus-Master. Interpretation of the
control word depends on the fieldbus option
installed and the control word profile selected
in 8-10 Control Profile.