Parameter Descriptions
0-38 Display Text 2
Range:
Function:
0
[0 -
Enter a text which can be viewed in the graphical
*
0 ]
display by selecting [38] Display Text 2 in
0-20 Display Line 1.1 Small, 0-21 Display Line 1.2
3
3
Small, 0-22 Display Line 1.3 Small, 0-23 Display Line 2
Large or 0-24 Display Line 3 Large.
0-39 Display Text 3
Range:
0
[0 -
Enter a text which can be viewed in the graphical
*
0 ]
display by selecting [39] Display Text 3in 0-20 Display
Line 1.1 Small, 0-21 Display Line 1.2 Small,
0-22 Display Line 1.3 Small, 0-23 Display Line 2 Large
or 0-24 Display Line 3 Large.
3.2.5 0-4* LCP Keypad
Enable, disable and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option:
[0] Disabled
[1] Enabled
[2] Password
[3] Hand Off/On When [Hand On] is pressed once, the LCP
[4] Hand Off/On
w. Passw.
0-41 [Off] Key on LCP
Option:
[0] Disabled
[1] Enabled
[2] Password Avoids unauthorised stop. If 0-41 [Off] Key on LCP
0-42 [Auto on] Key on LCP
Option:
[0] Disabled
[1] Enabled
32
Function:
Function:
No effect when [Hand On] is pressed. Select
[0] Disabled to avoid accidental start of the
frequency converter in Hand on mode.
The LCP switches to Hand on mode directly
when [Hand on] is pressed.
After pressing [Hand on] a password is
required. If 0-40 [Hand on] Key on LCP is in
included in My Personal Menu, define the
password in 0-65 Quick Menu Password.
Otherwise define the password in 0-60 Main
Menu Password.
switches to Off mode. When pressed again,
the LCP switches to Hand on mode.
Same as [3] but a password is required (see
[2]).
Function:
Avoids accidental stop of the frequency converter.
is included in the Quick Menu, then define the
password in 0-65 Quick Menu Password.
Function:
Avoid accidental start of the frequency converter
in Auto mode.
®
VLT
AutomationDrive FC 301/302 Programming Guide
0-42 [Auto on] Key on LCP
Option:
[2] Password Avoids unauthorised start in Auto mode. If
0-43 [Reset] Key on LCP
Option:
[0] Disabled
[1] Enabled
[2] Password
[7] Enabled
without OFF
[8] Password
without OFF
3.2.6 0-5* Copy/Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option:
[0]
No copy
*
[1]
All to LCP
[2]
All from LCP
[3]
Size indep. from
LCP
[4]
File from MCO to
LCP
[5]
File from LCP to
MCO
[6]
Data from DYN to
LCP
MG33MH02 - Rev. 2013-09-30
Function:
0-42 [Auto on] Key on LCP is included in the Quick
Menu, then define the password in 0-65 Quick
Menu Password.
Function:
No effect when [Reset] is pressed. Avoids
accidental alarm reset.
Avoids unauthorised resetting. If 0-43 [Reset]
Key on LCP is included in the Quick Menu,
then define the password in 0-65 Quick Menu
Password.
Resets the frequency converter without
setting it in Off mode.
Resets the frequency converter without
setting it in Off mode. A password is required
when pressing [Reset] (see [2]).
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Copies all parameters in all set-ups
from the frequency converter memory
to the LCP memory.
Copies all parameters in all set-ups
from the LCP memory to the frequency
converter memory.
Copy only the parameters that are
independent of the motor size. The
latter selection can be used to
programme several frequency
converters with the same function
without disturbing motor data.