Danfoss VLT AutomationDrive FC 301 Programming Manual page 24

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

How to Programme
4.
Press [OK]
5.
Disconnect the mains supply and wait until the
2
2
display turns off.
6.
Reconnect the mains supply - the frequency
converter is now reset.
14-22 Operation Mode initialises all except:
14-50 RFI Filter
8-30 Protocol
8-31 Address
8-32 FC Port Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Max Inter-Char Delay
15-00 Operating hours to 15-05 Over Volt's
15-20 Historic Log: Event to 15-22 Historic Log:
Time
15-30 Fault Log: Error Code to 15-32 Alarm Log:
Time
Manual initialisation
1.
Disconnect from mains and wait until the display
turns off.
2.
2a
2b
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This procedure initialises all except:
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
NOTICE
A manual initialisation also resets serial communication,
RFI filter settings (14-50 RFI Filter) and fault log settings.
22
VLT
Press [Status] - [Main Menu] - [OK] at
the same time while power up for LCP
102, Graphical Display
Press [Menu] - [OK] while power up for
LCP 101, Numerical Display
®
AutomationDrive FC 301/302 Programming Guide
MG33MH02 - Rev. 2013-09-30