Danfoss VLT AutomationDrive FC 301 Programming Manual page 19

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

How to Programme
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
5-12 Terminal 27 Digital Input
1-29 Automatic Motor Adaptation
(AMA)
3-02 Minimum Reference
3-03 Maximum Reference
3-41 Ramp 1 Ramp Up Time
3-42 Ramp 1 Ramp Down Time
3-13 Reference Site
Table 2.3 Quick Set-up Procedure
®
VLT
AutomationDrive FC 301/302 Programming Guide
OK
Set Nameplate frequency
OK
Set Nameplate current
OK
Set Nameplate speed in RPM
If terminal default is Coast
inverse it is possible to change
OK
this setting to No function. No
connection to terminal 27 is
then needed for running AMA
Set desired AMA function.
OK
Enable complete AMA is
recommended
Set the minimum speed of the
OK
motor shaft
Set the maximum speed of the
OK
motor shaft
Set the ramping up time with
OK
reference to synchronous
motor speed, n
Set the ramping down time
OK
with reference to synchronous
motor speed, n
Set the site from where the
OK
reference must work
MG33MH02 - Rev. 2013-09-30