Defining the analog input function - example
Advanced settings
Signal smoothing
When required, you can smooth the signal, which you read-in via an analog input, using
parameter p0753.
For more information, see the parameter list and in the function block diagrams 9566 ff of the
List Manual.
Specify deadband
Small signals of a few millivolts are often corrupted by interference in the cable. To be able
to enter a setpoint of exactly 0 V via an analog input, you must specify a deadband.
Figure 6-6
Deadband of the analog inputs
Table 6- 5
Parameter Description
p0764[0]
p0764[1]
6.2.3

Running the motor in jog mode (JOG function)

The "Jog" function is typically used to slowly move a machine part, e.g. a conveyor belt.
With the "Jog" function, you switch the motor on and off using a digital input. When the motor
is switched on, it accelerates to the jogging setpoint. There are two different setpoints
available, e.g. for motor counter-clockwise rotation and clockwise rotation.
The same ramp-function generator acts on the setpoint as for the ON/OFF1 command.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG
Deadband of the analog input
Settings of the deadband of the analog inputs
Deadband of the analog input AI0 (factory setting: 0)
Deadband of the analog input AI1 (Factory setting: 0)
In order to use the analog input AI 0 as the source for
the supplementary setpoint, you have to set
p1075 = 755[0].

Advanced commissioning

6.2 Inverter control
137