Tuning-Less Levels Setting (Fn200) Procedure - YASKAWA SGDV User Manual

Ac servo drives dc power input design and maintenance
Hide thumbs Also See for SGDV:
Table of Contents

Advertisement

Load Level
a) Using the utility function
To change the setting, refer to 6.2.2 Tuning-less Levels Setting (Fn200) Procedure.
Load Level
Mode 0
Mode 1 [Factory setting]
Mode 2
b) Using the parameter
Parameter
n.0
n.1
Pn170
[Factory setting]
n.2

6.2.2 Tuning-less Levels Setting (Fn200) Procedure

• To ensure safety, perform the tuning-less function in a state where the SERVOPACK can come to an
emergency stop at any time.
The procedure to use the tuning-less function is given below.
The digital operator or SigmaWin+ is required to execute this function.
For the basic operation of the digital operator, refer to
tor (Manual No.: SIEP S800000 55).
(1) Preparation
The following conditions must be met to perform the tuning-less function. The message "NO-OP" indicating
that the settings are not appropriate will be displayed, if all of the following conditions are not met.
• The tuning-less function must be enabled (Pn170.0 = 1).
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The test without a motor function must be disabled. (Pn00C.0 = 0).
(2) Operating Procedure
Use the following procedure.
Step
Display after Operation
1
2
Load level : Low
Load level : Medium
Load level : High
Meaning
Load level : Low (Mode 0)
Load level : Medium (Mode 1)
Load level : High (Mode 2)
CAUTION
Σ
-V Series User's Manual, Operation of Digital Opera-
Keys
6.2 Tuning-less Function
Meaning
When Enabled Classification
Immediately
Operation
Press the
Key to view the main menu for the
utility function.
Use the
or
Key to move through the list,
select Fn200.
Press the
Key to display the load level of the
tuning-less mode setting screen.
Notes:
• If the response waveform causes overshooting or if
the load moment of inertia exceeds the allowable
level (i.e., outside the scope of product guarantee),
press the
Key and change the mode setting to
2.
• If a high-frequency noise is heard, press the
Key and change the mode setting to 0.
Setup
6
6-13