10 Appendix
10.2.2 Parameters
Parameter
Size
No.
2
Input Signal Selection 1
4th 3rd 2nd 1st
digit digit digit digit
n.
Pn50A
10-20
Setting
Name
Range
0000 to FFF1
Input Signal Allocation Mode
0
Uses the sequence input signal terminals with the factory-set allocations.
1
Changes the sequence input signal allocation for each signal.
Servo ON (/S-ON) Signal Mapping
Signal Polarity: Normal; Servomotor power ON when ON (L-level)
Signal Polarity: Reverse; Servomotor power OFF when OFF (H-level)
0
Active when CN1-15 input signal is ON (L-level).
1
Active when CN1-16 input signal is ON (L-level).
2
Active when CN1-17 input signal is ON (L-level).
3
Active when CN1-18 input signal is ON (L-level).
4
Active when CN1-25 input signal is ON (L-level).
5
Active when CN1-26 input signal is ON (L-level).
6
Active when CN1-12 input signal is ON (L-level).
7
Always active (fixed).
8
Not active (fixed).
9
Active when CN1-15 input signal is OFF (H-level).
A
Active when CN1-16 input signal is OFF (H-level).
B
Active when CN1-17 input signal is OFF (H-level).
C
Active when CN1-18 input signal is OFF (H-level).
D
Active when CN1-25 input signal is OFF (H-level).
E
Active when CN1-26 input signal is OFF (H-level).
F
Active when CN1-12 input signal is OFF (H-level).
/P-CON Signal Mapping (P control when ON (L-level))
0 to F
Same as Servo ON Signal (/S-ON) Mapping.
P-OT Signal Mapping (Forward run prohibited when OFF (H-level))
0
Forward run allowed when CN1-15 input signal is ON (L-level).
1
Forward run allowed when CN1-16 input signal is ON (L-level).
2
Forward run allowed when CN1-17 input signal is ON (L-level).
3
Forward run allowed when CN1-18 input signal is ON (L-level).
4
Forward run allowed when CN1-25 input signal is ON (L-level).
5
Forward run allowed when CN1-26 input signal is ON (L-level).
6
Forward run allowed when CN1-12 input signal is ON (L-level).
7
Forward run prohibited.
8
Forward run allowed.
9
Forward run allowed when CN1-15 input signal is OFF (H-level).
A
Forward run allowed when CN1-16 input signal is OFF (H-level).
B
Forward run allowed when CN1-17 input signal is OFF (H-level).
C
Forward run allowed when CN1-18 input signal is OFF (H-level).
D
Forward run allowed when CN1-25 input signal is OFF (H-level).
E
Forward run allowed when CN1-26 input signal is OFF (H-level).
F
Forward run allowed when CN1-12 input signal is OFF (H-level).
Factory
When
Units
Setting
Enabled
2100
After restart
(cont'd)
Reference
Classification
Section
Setup
Reference
Section
3.3.1
Reference
Section
5.2.1
Reference
Section
6.9.3
Reference
Section
5.2.3