Steps for commissioning measuring cycles for the first time

10.2
10.2.1

General information

Manufacturer password must be set! (HMI\Commissioning\Password)
10.2.2
Step 0.1 – set up memory configuring machine data
• Set memory configuring machine data for measuring cycles (for data see Section 9.1
• The following machine data must be observed:
The following alarm is displayed after changes to the memory-configured parameters:
"4400 MD change results in reorganization of the buffered memory (loss of data!)"
The following operating sequences are needed to prevent data from being lost:
1. Read out NCK series machine start-up archive into the archive. (HMI\Services\>\Series
2. Read the read out NCK series machine back in.
10.2.3
Step 0.2 – set up other machine data
• Set other machine data for measuring cycles
• The following machine data must be observed:
• Then perform an NC reset. (HMI\Commissioning\NC reset)
Measuring cycles
Programming Manual, Release 04/2006, 6FC5398-4BP10-0BA0
"Machine data for executing measuring cycles" and the up-to-date information in
SIEMENSD.TXT / SIEMENSE.TXT included with the delivered software).
MD18118: MM_NUM_GUD_MODULES
MD18120: MM_NUM_GUD_NAMES_NCK
MD18130: MM_NUM_GUD_NAMES_CHAN
MD18150: MM_GUD_VALUES_MEM
MD18280: MM_NUM_FILES_PER_DIR
MD18320: MM_NUM_FILES_IN_FILESYSTEM
MD28082: MM_SYSTEM_FRAME_MASK
start-up)
(for data see Section 9.1 "Machine data for executing measuring cycles" and the up-to-
date information in SIEMENSD.TXT / SIEMENSE.TXT included with the delivered
software).
MD18170: MM_NUM_MAX_FUNC_NAMES
MD18180: MM_NUM_MAX_FUNC_PARAM
MD28020: MM_NUM_LUD_NAMES_TOTAL
MD28040: MM_NUM_LUD_VALUES_MEM
MD10132: MMC_CMD_TIMEOUT
MD11420: LEN_PROTOCOL_FILE
MD13200: MEAS_PROBE_LOW_ACTIV