Remaining Distance Operation - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Programmable controller
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Remaining distance operation

When pulse output is stopped by the pulse decelerate and stop command during positioning instruction operation and the
remaining distance operation enabled is ON, the remaining distance operation ready status is acquired. (Page 62
Remaining distance operation, Page 38 Pulse decelerate and stop) When the pulse decelerate and stop command turns off,
the remaining distance operation starts. Or if the external start signal (when enabled) is detected, remaining transfer amount
from deceleration stop is output. After the remaining distance operation is completed, the complete flag turns on. (Page
60 External Start Signal)
Acceleration
Command
Current position
Pulse decelerate
and stop command
Remaining distance
operation enabled
Remaining distance
operation start
*1
Complete flag
*1 The external start signal can start the remaining distance operation as well.
The following table shows applicable positioning instructions and control methods of the table operation.
Positioning instruction
Relative positioning (DRVI/DDRVI) instruction
Absolute positioning (DRVA/DDRVA) instruction
*2
Table operation (TBL
/DRVTBL/DRVMUL) instruction
*2 High-speed pulse input/output module is not supported.
Changes to the positioning address and command speed during positioning operation are valid until the system starts
deceleration stop under the pulse decelerate and stop command. After deceleration stop, changes are applied when the
positioning instruction is started again.
When dwell time is set, and the remaining distance operation start command is turned on immediately after deceleration stop,
remaining distance operation is started regardless of the dwell time.
time
Forced deceleration
stop by the pulse
decelerate and stop
command
Maximum
speed
speed
Remaining
transfer amount
Table operation control method
• 1: 1-speed positioning (relative address specification)
• 2: 1-speed positioning (absolute address specification)
• 6: Interrupt stop (relative address specification)
• 7: Interrupt stop (absolute address specification)
3 POSITIONING CONTROL FUNCTION
Deceleration
time
Bias speed
Positioning
address
3.4 Auxiliary Function
3
39

Advertisement

Table of Contents
loading

Table of Contents