The current address (user unit) functions within the range of -2147483648 to +2147483647. However, an overflow or
underflow occurs before the current address (pulse unit) is reached if the axis parameter is set in such a way that the number
of pulses per rotation is less than the number of transfer distance units per rotation. If that happens, overflow/underflow to the
upper or lower limit value is stored in the device.
■Current address (pulse unit)
The unit is the motor system unit (pulse unit), and the value indicated includes positioning data magnification. (Page 50
Unit Setting, Page 51 Position Data Magnification) The address range is -2147483647 to +2147483647.
Special Device
Name
F
CPU module
X
*1
Axis 1
Axis 2
Current
5
SD5502
SD5542
address
SD5503
SD5543
(pulse unit)
3
SD8340
SD8350
SD8341
SD8351
R: Read only, R/W: Read/Write
*1 5: FX5 dedicated device, 3: FX3 compatible device
When the value in the devices above changes, the current address (user unit) also changes automatically.
• Writing can be performed to the current address (pulse unit) of FX5 dedicated device only by the HCMOV/
DHCMOV instruction. During positioning operation, the value written to the current address is applied when
the instruction is completed.
• Reading can be performed to the current value by the HCMOV/DHCMOV instruction.
• In a program with interruption priority 1, the HCMOV/DHCMOV instruction specified with this device for
high-speed pulse input/output module cannot be executed. (MELSEC iQ-F FX5 User's Manual
(Application))
Precautions
The current address (pulse unit) functions with the range of -2147483647 to +2147483647 pulses. However, if the upper limit
is exceeded, current address overflows to the lower limit. If below the lower limit, current address underflows to the upper
limit.
High-speed pulse input/output module
First module
Axis 3
Axis 4
Axis 5
Axis 6
SD5582
SD5622
SD5662
SD5702
SD5583
SD5623
SD5663
SD5703
SD8360
SD8370
SD8361
SD8371
Second module
Third module
Axis 7
Axis 8
Axis 9
Axis 10 Axis 11 Axis 12
SD5742
SD5782
SD5822
SD5862
SD5743
SD5783
SD5823
SD5863
4 POSITIONING PARAMETER
R/W
Fourth module
SD5902
SD5942
R/W
SD5903
SD5943
R
4.2 Details of Parameters
4
57