Interrupt Stop (Absolute Address Specification) - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Programmable controller
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Operation of the complete flags
The following describes the operation timings of the complete flags.
If dwell time is specified, the flag turns on after the dwell time elapses.
FX3 compatible (Effective only at TBL instruction or
DRVTBL instruction execution)
Instruction execution
complete flag
(SM8029)
ON
From when pulse output of
condition
the specified positioning
address is completed or
when deceleration stop is
started by an interrupt
input to when the drive
contact is turned off
ON → OFF
When the drive contact is turned off
condition
*1 The flag turns on only for one scan when the drive contact of the instruction turns from OFF to ON.
*2 When remaining distance operation enabled is turn on, abnormal end flag is not turn on. (Page 62 Remaining distance operation
enabled)
*3 Only high-speed pulse input/output module is supported.

Interrupt Stop (Absolute Address Specification)

The following explains control method [7: Interrupt Stop (Absolute Address Specification)].
Setting data
The following table shows the operand assignment.
*1
Operand 1
Description
Positioning Address
Range
-2147483648 to +2147483647
(User system unit)
Details
Set the absolute address within
the range of -2147483648 to
*4
+2147483647
in pulse.
*1 The positioning address can be changed during positioning operation. (Page 36) However, only the last table accepts the change in
the case of continuous operation.
*2 Command speed can be changed during positioning operation. (Page 37)
*3 When the positioning table data is set to use device, the value can be changed during positioning operation. The change is applied when
the table operation instruction is restarted.
*4 Set the number of output pulses per table execution to 2147483647 or lower.
Instruction execution abnormal
end flag
(SM8329)
From when the following operation or
function is completed to when the drive
contact is turned off
*1
• The axis is already used.
• Pulse output stop command
• Pulse decelerate and stop command
• Limit of the moving direction
• All module reset when a stop error
*3
occurs
• All outputs disabled (SM8034)
• Positioning address error
• Deceleration stop after the command
speed is changed to 0
• Table shift cannot be completed in time
*2
Operand 2
Command Speed
1 to 2147483647
(User system unit)
Set the speed within the range of
1 pps to 200 Kpps in pulse.
User specification (Effective only at DRVTBL instruction
or DRVMUL instruction execution)
Instruction execution
Instruction execution abnormal
complete flag
end flag
From when pulse output of
From when the following operation or
the specified positioning
function is completed to when the ON →
address is completed or
OFF condition is met
when deceleration stop is
• The axis is already used.
started by an interrupt
• The drive contact is turned off during
*2
input to when the ON →
positioning operation
OFF condition is met
• Pulse output stop command
• Pulse decelerate and stop command
• Limit of the moving direction
• All module reset when a stop error
occurs
• All outputs disabled (SM8034)
• Write during RUN
• Positioning address error
• Deceleration stop after the command
speed is changed to 0
• Table shift cannot be completed in time
The flag remains on until either of the following is performed.
• Turning off the flag by the user
• Restarting the table instruction
• Shift to the next table
*3
Operand 3
Dwell Time
0 to 32767 (ms)
Dwell time is time until the
complete flag turns on after the
positioning address is reached
(interrupt stop).
6.2 Operations of Control Method
*2
*3
*3
Operand 4
Interrupt Counts
1 to 32767
This is the count of inputs that are
necessary for interrupt. The
setting is enabled only in the high-
speed mode.
6 TABLE OPERATION
175
6

Advertisement

Table of Contents
loading

Table of Contents