All parameters
No.
Name/Value
DISABLE
ENABLE
31 AUTOMATIC
RESET
3101 NR OF TRIALS Defines the number of automatic fault resets the drive
0...5
3102 TRIAL TIME
1.0...600.0 s
3103 DELAY TIME
0.0...120.0 s
3104 AR
OVERCURRE
NT
DISABLE
ENABLE
3105 AR
OVERVOLTAG
E
DISABLE
ENABLE
3106 AR
UNDERVOLTA
GE
DISABLE
ENABLE
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
No action
The drive trips on fault OUTP WIRING.
Automatic fault reset. Automatic resets are possible only for
certain fault types and when the automatic reset function is
activated for that fault type.
performs within the time defined by parameter
TIME.
If the number of automatic resets exceeds the set number
(within the trial time), the drive prevents additional automatic
resets and remains stopped. The drive must be reset from
control panel or from a source selected by parameter
FAULT RESET SEL.
Example: Three faults have occurred during the trial time
defined by parameter 3102. Last fault is reset only if the
number defined by parameter 3101 is 3 or more.
Trial time
X
X X
Number of the automatic resets
Defines the time for the automatic fault reset function. See
parameter
NR OF TRIALS.
3101
Time
Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter
TRIALS. If delay time is set to zero, the drive resets
immediately.
Time
Activates/deactivates the automatic reset for the
overcurrent fault. Automatically resets the fault
(OVERCURRENT) after the delay set by parameter
DELAY TIME.
Inactive
Active
Activates/deactivates the automatic reset for the
intermediate link overvoltage fault. Automatically resets the
fault (DC OVERVOLT) after the delay set by parameter
DELAY TIME.
3103
Inactive
Active
Activates/deactivates the automatic reset for the
intermediate link undervoltage fault. Automatically resets
the fault (DC UNDERVOLTAGE) after the delay set by
parameter
DELAY TIME.
3103
Inactive
Active
Actual signals and parameters 199
3102
X = Automatic reset
t
3101
Def/FbEq
0
1
0
TRIAL
1604
1 = 1
30.0 s
1 = 0.1 s
0.0 s
NR OF
1 = 0.1 s
DISABLE
3103
0
1
DISABLE
0
1
DISABLE
0
1

Hide quick links: