Electrical Installation

7 Electrical Installation

7.1 Connections

7.1.1 Torque Settings

When tightening electrical connections, it is important to use a torque wrench to obtain the correct torque. Torque that is
too low or too high results in a bad electrical connection.
See the torque settings in Table 7.1.
Frame size
D1h/D3h/D5h/D6h
7
7
D2h/D4h/D7h/D8h
E
F
Table 7.1 Terminal Tightening Torques
160
®
VLT
Terminal
Size
Mains
M10
Motor
Load sharing
Regeneration
Earth (ground)
M8
Brake
Mains
M10
Motor
Regeneration
Load Sharing
Earth (ground)
Brake
M8
Mains
M10
Motor
Load Sharing
Earth
Regen
M8
Brake
Mains
M10
Motor
Load Sharing
Regen:
DC-
M8
DC+
M10
F8-F13 Regen
M10
Earth
M8
Brake
AutomationDrive FC 300 Design Guide 90-1200 kW
Torque nominal [Nm (in-lbs)]
29.5 (261)
14.5 (128)
29.5 (261)
19.1 (169)
9.5 (85)
19.1 (169)
9.5 (85)
19.1 (169)
19.1 (169)
9.5 (85)
MG34S202 - Rev. 2013-08-19
Torque range [Nm (in-lbs)]
19-40 (168-354)
8.5-20.5 (75-181)
19-40 (168-354)
8.5-20.5 (75-181)
17.7-20.5 (156-182)
8.8-10.3 (78.2-90.8 in-lbs.)
17.7-20.5 (156-182 in-lbs.)
8.8-10.3 (78.2-90.8)
17.7-20.5 (156-182)
17.7-20.5 (156-182.)
8.8-10.3 (78.2-90.8)