RS-485 Installation and Set...
Parameter block
The parameter block is used to transfer parameters between master and follower. The data block is made up of 12 bytes (6
words) and also contains the process block.
STX
Illustration 10.7 Parameter block
Text block
The text block is used to read or write texts via the data block.
STX
LGE
Illustration 10.8 Text Block
10.7.7 The PKE Field
The PKE field contains 2 sub fields:
•
Parameter command and response AK
•
Parameter number PNU
10
10
AK
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Illustration 10.9 PKE Field
Bits no. 12–15 transfer parameter commands from master
to follower and return processed follower responses to the
master.
244
LGE
ADR
PKE
IND
ADR
PKE
IND
PKE
IND
PWE
high
PNU
®
VLT
AutomationDrive FC 300 Design Guide 90-1200 kW
PWE
PWE
high
low
Ch1
Ch2
Chn
Bit no.
15
14
0
0
0
0
0
0
0
0
1
1
PWE
low
1
1
1
1
Table 10.3 Parameter Commands Master⇒Follower
Bit no.
15
14
0
0
0
0
0
0
0
1
1
1
Table 10.4 Response Follower⇒Master
MG34S202 - Rev. 2013-08-19
PCD1
PCD2
PCD1
PCD2
Parameter command
13
12
0
0
No command
0
1
Read parameter value
1
0
Write parameter value in RAM (word)
1
1
Write parameter value in RAM (double
word)
0
1
Write parameter value in RAM and
EEprom (double word)
1
0
Write parameter value in RAM and
EEprom (word)
1
1
Read/write text
Response
13
12
0
0
No response
0
1
Parameter value transferred (word)
1
0
Parameter value transferred (double
word)
1
1
Command cannot be performed
1
1
text transferred
BCC
BCC