Electrical Installation
Input Polarity of Control Terminals
PNP (Source)
Digital input wiring
12
13
18
19
27
Illustration 7.50 Input Polarity of Control Terminals
NPN (Sink)
Digital input wiring
12
13
18
19
27
Illustration 7.51 Input Polarity of Control Terminals
7.5.9 Relay Output D Frame
Relay 1
•
Terminal 01: common
•
Terminal 02: normally open 400 V AC
•
Terminal 03: normally closed 240 V AC
®
VLT
AutomationDrive FC 300 Design Guide 90-1200 kW
29
32
33
20
37
29
32
33
20
37
MG34S202 - Rev. 2013-08-19
Relay 2
•
Terminal 04: common
•
Terminal 05: normally open 400 V AC
•
Terminal 06: normally closed 240 V AC
Relay 1 and relay 2 are programmed in 5-40 Function Relay,
5-41 On Delay, Relay, and 5-42 Off Delay, Relay.
Use option module MCB 105 for additional relay outputs.
relay1
relay2
Illustration 7.52 D-Frame Additional Relay Outputs
7.5.10 Relay Output E & F-Frame
Relay 1
•
Terminal 01: common
•
Terminal 02: normally open 240 V AC
•
Terminal 03: normally closed 240 V AC
Relay 2
•
Terminal 04: common
•
Terminal 05: normally open 400 V AC
•
Terminal 06: normally closed 240 V AC
Relay 1 and relay 2 are programmed in 5-40 Function Relay,
5-41 On Delay, Relay, and 5-42 Off Delay, Relay.
Use option module MCB 105 for additional relay outputs.
03
240Vac, 2A
02
400Vac, 2A
01
06
240Vac, 2A
05
400Vac, 2A
04