Installing Control Cables - Danfoss VLT AutomationDrive FC 300 Design Manual

90-1200 kw
Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

Electrical Installation

7.5.7 Installing Control Cables

Electrical Installation
3 Phase
power
input
Load Share
+10Vdc
7
7
-10 VDC - +10VDC
0/4-20 mA
-10 VDC - +10VDC
0/4-20 mA
Illustration 7.43 Interconnect Diagram, D-Frame Frequency Converters (A=analog, D=digital)
Terminal 37 is used for Safe Torque Off. For Instructions on Safe Torque Off Installation, Refer to 3.12 Safe Torque Off.
204
®
VLT
AutomationDrive FC 300 Design Guide 90-1200 kW
TB5
230 VAC
R1
Anti-condensation heater (optional)
50/60Hz
(optional)
TB6 Contactor
230 VAC
50/60Hz
91 (L1)
92 (L2)
93 (L3)
95
PE
88 (-)
89 (+)
50 (+10 V OUT)
A53 U-I (S201)
53 (A IN)
ON=0-20mA
A54 U-I (S202)
OFF=0-10V
54 (A IN)
55 (COM A IN)
12 (+24V OUT)
13 (+24V OUT)
18 (D IN)
19 (D IN)
20 (COM D IN)
27
(D IN/OUT)
24V
0V
29
(D IN/OUT)
24V
0V
32 (D IN)
33 (D IN)
37 (D IN)
Switch Mode
Power Supply
10Vdc
24Vdc
15mA
200mA
+
-
+
-
P 5-00
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
S801/Bus Term.
24V (NPN)
OFF-ON
0V (PNP)
5V
24V (NPN)
0V (PNP)
S801
RS-485
Interface
24V (NPN)
0V (PNP)
24V (NPN)
0V (PNP)
MG34S202 - Rev. 2013-08-19
(U) 96
(V) 97
(W) 98
(PE) 99
Regen +
(R+) 82
Brake
Regen
resistor
(R-) 81
Regen - 83
Relay1
03
240Vac, 2A
02
400Vac, 2A
01
Relay2
06
240Vac, 2A
05
400Vac, 2A
04
(COM A OUT) 39
Analog Output
0/4-20 mA
(A OUT) 42
ON=Terminated
1
OFF=Open
Brake Temp
(NC)
2
0V
RS-485
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
(PNP) = Source
(NPN) = Sink
Motor

Advertisement

Table of Contents
loading

Table of Contents