Electrical Installation
7.2.6 Supplementary Fuses
Supplementary Fuses
Frame size
D
Table 7.39 D-frame Anti-Condensation Heater Fuse Recommendation
NOTICE
If a D-frame frequency converter comes with an anti-condensation heater, the heater must be powered, controlled, and
protected by the installing contractor.
Frame size
E and F
Table 7.40 SMPS Fuse
Size/Type
P355-P400, 525-690 V
P315-P800, 380-500 V
P500-P1M2, 525-690 V
Table 7.41 Fan Fuses
2.5-4.0 A Fuse
P450-P800, 380-500 V
P630-P1M2, 525-690 V
4.0-6.3 A Fuse
P450-P800, 380-500 V
P630-P1M2, 525-690 V
6.3-10 A Fuse
P800600HP-1200HP,
P630-P1M2, 525-690 V
10-16 A Fuse
P450-P800, 380-500 V
P630-P1M2, 525-690 V
Table 7.42 Manual Motor Controller Fuses
Frame Size
Bussmann PN
F
LPJ-30 SP or SPI
Table 7.43 30 A Fuse Protected Terminal Fuse
Frame size
Bussmann PN
F
LPJ-6 SP or SPI
Table 7.44 Control Transformer Fuse
®
VLT
AutomationDrive FC 300 Design Guide 90-1200 kW
Bussmann PN
LPJ-21/2SP
Bussmann PN
KTK-4
Bussmann PN
KTK-4
Size/Type
Bussmann PN
LPJ-6 SP or SPI
LPJ-10 SP or SPI
LPJ-10 SP or SPI
LPJ-15 SP or SPI
P450-
LPJ-15 SP or SPI
380-500 V
LPJ-20 SP or SPI
LPJ-25 SP or SPI
LPJ-20 SP or SPI
Rating
30 A, 600 V
Rating
6 A, 600 V
MG34S202 - Rev. 2013-08-19
Rating
2.5 A, 600 V
Rating
4 A, 600 V
LittelFuse
KLK-15
KLK-15
Rating
6 A, 600 V
Element, Time Delay, 6 A
10 A, 600 V
Element, Time Delay, 10 A
10 A, 600 V
Element, Time Delay, 10 A
15 A, 600 V
Element, Time Delay, 15 A
15 A, 600 V
Element, Time Delay, 15 A
20 A, 600 V
Element, Time Delay, 20 A
25 A, 600 V
Element, Time Delay, 25 A
20 A, 600 V
Element, Time Delay, 20 A
Alternative fses
Any listed Class J Dual Element, Time Delay, 30 A
Alternative fuses
Any listed Class J Dual Element, Time Delay, 6 A
Rating
4 A, 600 V
15 A, 600 V
15 A, 600 V
Alternative fuses
Any listed Class J Dual
Any listed Class J Dual
Any listed Class J Dual
Any listed Class J Dual
Any listed Class J Dual
Any listed Class J Dual
Any listed Class J Dual
Any listed Class J Dual
193