Connecting the motor power - X2

Converter side
X2
Terminal Designation
U
V
W
Motor side
1FL2 shaft heights 20, 30, and 40
Motor power interface
Hybrid connector
1FL2 shaft heights 48 and 52
Motor power interface
M17 angular connector
1FL2 shaft heights 45, 65, and 90
Motor power interface
M23 angular connector
18
Motor phase U
Motor phase V
Motor phase W
Pin
Designation
U
Phase U
V
Phase V
W
Phase W
PE
Protective grounding
+
Holding brake, positive
-
Holding brake, negative
A
Encoder power supply, 5 V
B
Encoder power supply, reference ground
C
Absolute encoder clock signal, positive
D
Absolute encoder clock signal, negative
E
Absolute encoder data signal, positive
F
Absolute encoder data signal, negative
Pin
Designation
U
Phase U
V
Phase V
W
Phase W
PE
Protective grounding
A
Holding brake, positive
B
Holding brake, negative
Pin
Designation
1
Phase U
2
Phase V
3
Phase W
PE
Protective grounding
Technical data
Maximum current limit: 20 A