16.3.4 Testing the direction of traverse
Test the controls for the direction of traverse according to the following diagram (effective machine
parameters: MP210 count direction of the measuring system signals, MP1040 polarity of the
nominal value voltage, MP1320 direction of traverse on passing over the reference marks).
Modify
MP210
MP1040
MP1320
Ref. approach
with start key
Is
direction of
NO
traverse correct?
(determined
by MP1320)
YES
Check direction of traverse of
ref. approach for all axes
This flow diagram must be worked through for every axis!
01.98
TNC 407/TNC 415/TNC 425
Switch on line voltage
YES
direction of traverse
traverse wrong when
Reset current interruption with CE
Switch on control voltage:
axes are in control loop
NO
correct? (determined
Check direction of traverse
for all axes
16 Commissioning and start-up procedure
START
Was
"gross positioning
error"
or
wrong or direction
approaching
ref. marks
?
NO
Gross "positioning
error" (MP1040
or MP210 wrong)
?
NO
Start ref. approach
with axis direction
keys
?
YES
Is
direction of
traverse of axes
by MP1040 and
MP210)
Switch
off line
voltage
YES
(both ref.
approach
modes must
be run!)
NO
4-263