Install a DPCC
The connector (back) side of the DPCC faces inward toward the server.
Slide the DPCC into the slot until it stops (1).
4.
This leaves the DPCC protruding slightly from the back of the server. Do not attempt push the
DPCC inward beyond this point.
5.
Rotate the lever on the DPCC upward until it locks into place (2).
Caution -
This action draws the DPCC inward, engaging the connectors in the DPCC with the connectors
on the server midplane.
6.
Use a stylus to press one or both ATTN buttons on the front of the DPCC.
Note -
are doing cold service, this step is not necessary.
The buttons alert the system to a request to bring the devices online. When the system
acknowledges the request, it lights the DPCC OK indicators on the DPCC.
Verify that the green OK indicators on the front of the DPCC are on steady.
7.
158
Oracle Server X7-8 Service Manual • April 2018
Pinch point. Keep fingers away from the backside of the lever when closing it.
If only a single PCIe card is present, press only the corresponding ATTN button. If you