Torque (Magnetic Flux) Setting Current (Voltage) Bias And Gain - Mitsubishi Electric FR-E800 Series Instruction Manual

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

13.5
Torque (magnetic flux) setting current (voltage)
bias and gain
Sensorless Vector
Sensorless
Sensorless
PM
PM
PM
Vector
Vector
The magnitude (slope) of the torque can be set as desired in relation to the torque setting signal (0 to 5 VDC, 0 to 10 VDC, or
0 to 20 mA).
Use Pr.267 Terminal 4 input selection to switch among input 0 to 5 VDC, 0 to 10 VDC, and 0 to 20 mA. (Refer to
Pr.
Name
C38 (932)
Terminal 4 bias command (torque/
*1
magnetic flux)
T410
C39 (932)
Terminal 4 bias (torque/magnetic
*1
flux)
T411
C40 (933)
Terminal 4 gain command (torque/
*1
magnetic flux)
T412
C41 (933)
Terminal 4 gain (torque/magnetic
*1
flux)
T413
241
Analog input display unit
M043
switchover
*1
On the LCD operation panel used as the command source, the parameter number in parentheses appears instead of that starting with the letter C.
 Changing the function of analog input terminal
• In the initial setting, terminal 4 is used for analog input of the speed command (speed limit). To use the analog input
terminal to input the torque command, torque limit, or magnetic flux command, set Pr.858 Terminal 4 function
assignment to change the function. (Refer to
 Relationship between the analog input terminal function and the
calibration parameter
• Calibration parameter according to the terminal 4 function
Pr.858
Terminal function
setting
0 (initial
Frequency (speed) command /
value)
speed limit
4
Torque limit
6
Torque bias input
9999
No function
 Changing the torque for the maximum analog input (C40 (Pr.933))
• Use C40 (Pr.933) to change the torque setting (gain) for the maximum analog input current (voltage).
 Analog input bias/gain calibration (C38 (Pr.932) to C41 (Pr.933))
• The "bias"/"gain" function can adjust the relation between the torque and the torque limit setting input signal. Examples of
setting input signals are 0 to 5 VDC, 0 to 10 VDC, or 0 to 20 mADC, and they are externally input.
• Set the bias torque of the terminal 4 input using C38 (Pr.932). (The initial value is the torque for 0 mA.)
Initial
Setting range
value
0%
0% to 400%
0%
0% to 300%
150%
0% to 400%
100%
0% to 300%
0
0
1
page
315.)
Bias setting
C5 (Pr.904) Terminal 4 frequency setting
bias frequency
C6 (Pr.904) Terminal 4 frequency setting
bias
C38 (Pr.932) Terminal 4 bias command
(torque/magnetic flux)
C39 (Pr.932) Terminal 4 bias (torque/
magnetic flux)
C38 (Pr.932) Terminal 4 bias command
(torque/magnetic flux),
C39 (Pr.932) Terminal 4 bias (torque/
magnetic flux)

13.5 Torque (magnetic flux) setting current (voltage) bias and gain

Description
Set the bias torque (magnetic flux) for the terminal 4
input.
Set the converted % of the bias current (voltage) for the
terminal 4 input.
Set the gain (maximum) torque (magnetic flux) for the
terminal 4 input.
Set the converted % of the gain current (voltage) for the
terminal 4 input.
% display
Select the unit for analog input
display.
V/mA display
Calibration parameter
Gain setting
Pr.126 Terminal 4 frequency setting gain
frequency
C7 (Pr.905) Terminal 4 frequency setting
gain
C40 (Pr.933) Terminal 4 gain command
(torque/magnetic flux)
C41 (Pr.933) Terminal 4 gain (torque/
magnetic flux)
C40 (Pr.933) Terminal 4 gain command
(torque/magnetic flux)
C41 (Pr.933) Terminal 4 gain (torque/
magnetic flux)
13. (T) Multi-Function Input Terminal Parameters
11
12
13
page
310.)
14
15
16
17
18
19
20
323