HART function

8.4 Tags

8.4
Tags
8.4.1

Notes on HART variables

Introduction
HART variables, the properties dialog and address assignment are explained below.
HART variables (Page 86)
8.4.2

HART variables

Definition
Each HART variable consists of a 4-byte real value and one byte of quality code. A maximum of
four HART variables supported by the connected field device are read cyclically for each channel
with enabled HART functionality. The HART variables are read automatically via the HART
command 3 (for field devices with HART Rev. 5 and 6) or via command 9 (for field devices with
HART Rev. 7 or later).
These four HART variables are always stored in the HART variable data record 121 for each
channel and can be read at any time.
HART variable data record (Page 105)
Description
The following HART variables are available:
• PV (Primary Variable)
• SV (Secondary Variable)
• TV (Tertiary Variable)
• QV (Quaternary Variable)
8.4.3

Quality code

Definition
The quality code describes the process status of the corresponding HART variable.