50/58
Siemens
Building Technologies
12
Support for errors and faults
12.1
Error/fault code list
The list only describes errors and faults that may occur when connecting and operating
the bus operator unit.. See the descriptions of the related devices for information on
other error codes.
Number
Cause of error/fault
6001
>1 identical device address
12.2
Troubleshooting
Fault / Fault status message
When creating the device list (Create list,
Add devices), devices outside the search
range will also be included on the list.
Caution!
Device version not supported
Caution!
Device not responding
Data does not show real value (e.g.
room temperature 655.3 °C).
Data point setting has no effect.
Device switches on and off
independently.
Background illumination of display very
low.
Operating values of bus devices not
displayed properly or cannot be
changed.
Bus operator unit RMZ792 Series B
12 Support for errors and faults
Effect
Urgent message; must be
acknowledged.
Cause / Solution
The device address of the bus operator
unit (area.line.address) and/or of other
bus devices does not match the current
bus topology.
Check and correct device addresses as
needed.
The version of the device description of
the bus operator unit and the software
version of the target device do not
match.
• Determine which versions of internal
memory and target device are
compatible.
• Exchange bus operator unit or target
device.
No communication with target device.
• Is the device operating?
• Is the device connected to the KNX
bus?
• Was the device address changed?
The data point in the current
configuration is useless (device does not
support data point visibility).
The data point in the current
configuration is useless (device does not
support data point visibility).
• Power is supplied to the bus operator
unit via KNX. Bus supply is
dimensioned insufficiently and cannot
fully supply the bus operator unit. Use
bigger bus supply, or
• Supply external AC 24 V power to the
bus operator unit.
CE1P3113en
07.07.2011