11.7.2
Technical specifications - Ex power module
Ex power module with intrinsically safe output voltage (Ex-PM E)
Note the potentially lower permissible operating temperature of all components contained in
the basic design of the distributed I/O and any derating (see section "Derating for the Ex power
module (Page 114)").
Article number
General information
Product type designation
usable BaseUnits
Product function
•
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption, max.
from load voltage L+ (without load), max.
Output voltage
Rated value (DC)
Overvoltage protection
Output current
horizontal installation
•
•
vertical installation
•
•
Power
Power available from the backplane bus
Power loss
Power loss, typ.
Interrupts/diagnostics/status information
Diagnostics function
Diagnoses
•
•
Diagnostics indication LED
•
•
•
Modules for devices in a hazardous area
System Manual, 04/2021, A5E50165138-AA
11.7 Technical specifications of subcomponents of the Ex module group
I&M data
up to 60 °C, max.
up to 70 °C, max.
up to 50 °C, max.
up to 60 °C, max.
Diagnostic information readable
missing load voltage
MAINT LED
Monitoring of the supply voltage (PWR-LED)
for module diagnostics
Technical specifications
6DL1133-6PX00-0HW0
Ex-PM-E
BU type W0
Yes; Asset data
24 V
19.2 V
28.8 V
Yes
1.4 A
50 mA
24 V
Yes
0.8 A
0.6 A
0.8 A
0.6 A
100 mW
4.8 W
Yes
Yes
Yes
Yes; Yellow LED
Yes; green PWR LED
Yes; green/red DIAG LED
113