WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
8.6.1.3
Diagnostics of External Module/Channel Errors
Table 40: Parameterization DAP – Attribute Diagnostics of External Module/Channel Errors
Attribute Name
Diagnostics of external
module/channel errors
8.6.1.4
Process Data Representation
Table 41: Parameterization DAP – Process Data Representation
Attribute Name
Process data
representation
8.6.1.5
Response to PROFINET IO failure
Table 42: Parameterization DAP – Attribute Response to PROFINET IO failure
Attribute Name
Response to
PROFINET IO failure
Manual
Version 2.0.0
Attribute Value
Description
The external diagnostic information of all
diagnosable modules
•
disabled
*)
enabled
•
*)
Default settings
Attribute Value
Description
Word or double-word-oriented process data are
transmitted to the PROFINET IO master in
INTEL (LSB-MSB)
•
MOTOROLA
•
*)
(MSB-LSB)
*)
Default settings
Attribute Value
Description
In the event of a malfunction of the PROFINET IO
communication, the status of the available output
periphery can be influenced in various ways
•
K-Bus transmission
stops
output image is
•
stored
substitute values are
•
*)
switched
output image is
•
cleared
*)
Default settings
Commissioning
not transmitted to the PROFINET IO
controller.
transmitted to the PROFINET IO controller.
"Little Endian" format.
"Big Endian" format.
the process data exchange on the internal bus
is stopped, all outputs are switched off after a
module specific monitoring time of 100 ms.
all outputs maintain the last status before the
malfunction.
the substitute values parameterized on the part
of the output submodules are output.
the output data is of the corresponding
peripheral modules set to zero.
97