750-370 PROFINET IO Fieldbus Coupler
Table 172: "ExtChannelDiagnosisData" Instance Structure
Byte-
Date typE
offset
4 / 5
WORD
6 / 7
WORD
8 / 9
DWORD
10 / 11
The following tables describe the possible fault messages that are based on the
combination of fault type, extended fault type and additional value. The "xx"
symbols used for some additional values represent the signal channel
(0x0000 ... 0x0007) where the fault has been detected.
The faults described in the following table are faults occurring when configuring
both the station substitute (fieldbus coupler) and the modules (I/O modules).
Configuration faults are coded using fault type 0x0010 in accordance with the
PROFINET IO standard.
Table 173: Additional Error Information Error Type "Configuration Fault (0x0010)"
Fault type "Configuration fault (0x0010)"
Extended
fault type
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
0x000A
0x000B
0x000C
0x000D
0x0010
0x0011
0x0014
0x0020
Manual
Version 2.0.0
Description
Error Type
0x0000 reserved, not specified
0x0010 Parameterization fault
0x001F Missing Parameterization
0x0100 Internal bus fault
Extended Error Type
0x0000
...
0xFFFF
Additional value
Additional
Description
value
0xC0018001
The module type (Identifier) is not recognized.
0xC0018002
The module type (Identifier) is invalid.
0xC0018003
The status of the module is not allowed during configuration.
0xC0018004
The length of the configuration data for the module is smaller
than expected.
0xC0018005
The length of the configuration data for the module is larger than
expected.
0xC0018006
The received configuration data for the module is not supported.
0xC0018007
The characteristics (Property) for the module are not supported.
0xC0018008
The reserved module parameters have an invalid value.
0xC001800A
Parameters are not permissible.
0xC001800B
Index of dataset is not allowed.
0xC001800C
Fault when accessing module registers.
0xC001800D
Data length is invalid when accessing module registers.
0xC0018010
The substitute value behavior for the inputs of the module is not
supported.
0xC0018011
The substitute value behavior for the inputs of the module is not
allowed.
0xC0018014
The reserved input parameters of the module have an invalid
value.
0xC0018020
The substitute value behavior for the outputs of the module are
not supported.
Extended Error Description
Additional error description
Appendix