14.5.1.2.3 Analog Input Modules

Table 169: Fault Cases of Analog Output Modules with Diagnostics Capability

Item
number
75x-460,
75x-461,
75x-481
75x-469
75x-487
750-450,
750-451,
75x-464
75x-452,
75x-465,
75x-467,
75x-468,
75x-470
75x-472,
75x-475,
75x-477
75x-453,
75x-454,
75x-455,
75x-456,
75x-457,
75x-459,
75x-466,
75x-474,
75x-476,
75x-478,
75x-479,
75x-480,
75x-483,
750-485,
750-486,
75x-492
75x-491 WORD
75x-493 WORD
75x-494,
75x-495
Data
Error type
format
WORD
0x0006 / 6
0x0008 / 8
0x0009 / 9
WORD
0x0001 / 1
0x0006 / 6
0x0007 / 7
0x0008 / 8
0x0009 / 9
WORD
0x0007 / 7
0x0009 / 9
WORD
0x0007 / 7
0x0008 / 8
0x0009 / 9
0x0003 / 3
0x0007 / 7
0x0009 / 9
0x0002 / 2
OTHER 0x0009 / 9
750-370 PROFINET IO Fieldbus Coupler
Explanation
Line break
Signal line to transmitter interrupted
Lower limit value
Measurement range undershoot or signal
undershot
line to the transmitter has a short circuit
Error
Internal error (e. g. hardware error)
Short circuit
Signal line to transmitter short circuit
Line break
Signal line to transmitter interrupted
Upper limit value
Upper measurement range end value
exceeded
exceeded
Lower limit value
Lower measurement range end value
undershot
undershot
Error
Internal error (e. g. hardware error)
Upper limit value
Upper measurement range end value
exceeded
exceeded
Error
Internal error (e. g. hardware error)
Upper limit value
Upper measurement range end value
exceeded
exceeded
Lower limit value
Lower measurement range end value
undershot
undershot
Error
Internal error (e. g. hardware error)
Overvoltage
Maximum permissible bridge power
Upper limit value
supply
exceeded
Overrange bridge voltage
Error
Internal error (e. g. hardware error)
Undervoltage
Low voltage threshold between L and N
undershot
Error
Error on at least one phase or I/O module
faulty.