Table 174: Additional Error Information Fault Type "Missing Parameters 0X001F - WAGO 750-370 Manual

Profinet io fieldbus coupler 2-port; 100 mbit/s; digital and analog signals
Hide thumbs Also See for 750-370:
Table of Contents

Advertisement

WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Table 173: Additional Error Information Error Type "Configuration Fault (0x0010)"
Fault type "Configuration fault (0x0010)"
Extended
fault type
0x009C
0x009D
0x009E
0x009F
0x00A0
0x00A1
0x00A2
0x00A3
0x00A4
0x00A5
0x00A6
...
0x00B2
0x00B3
0x00B4
0x00B5
0x00B6
0x00B7
Missing parameters for both the station substitute (fieldbus coupler) and the
modules (I/O modules) are also reported using an extended channel diagnostics.
Fault type 0x001F is classified as missing parameters in accordance with the
standard.

Table 174: Additional Error Information Fault type "Missing Parameters 0x001F"

Fault type "Missing parameters (0x001F)"
Extended
fault type
0x0009
Faults occurring on the internal data bus system are also indicated by transmitting
an extended channel diagnostics. This is a manufacturer specific fault that is
displayed using the fault type 100
the following table.
Manual
Version 2.0.0
Additional
Description
value
0xC001809C
The integration of control and status data of complex modules
(Table 0, register 3) is activated.
0xC001809D
Formatting of complex module data (Table 0, register 3) is not
allowed.
0xC001809E
Formatting of digital module data (Table 0, register 3) is not
allowed.
0xC001809F
The data allocation (Table 0, register 3) is not allowed (neither
bytes nor words).
0xC00180A0
The setting for updating the input data (Table 0, register 3) is not
allowed (not asynchronous).
0xC00180A1
The setting for updating the output data (Table 0, register 3) is
not allowed (not asynchronous).
0xC00180A2
The setting for the behavior of fieldbus faults (Table 0, register
3) is not allowed.
0xC00180A3
The setting for the behavior of internal data bus faults (Table 0,
register 3) is not allowed.
0xC00180A4
The setting for activating the diagnostics (Table 0, register 3) is
not allowed.
0xC00180A5
The linking of the diagnostic data to the process image (Table 0,
register 3) is activated.
0xC00180A6
The reserved station parameters (Table 0, register 4) have invalid
values.
...
...
0xC00180B2
The reserved station parameters (Table 0, register 4) have invalid
values.
0xC00180B3
The reserved station parameter (Table 100, register 75) have
invalid values.
0xC00180B4
The module setting (Table 100, register 75) is not allowed.
0xC00180B5
The reserved station parameter (Table 100, register 76) have
invalid values.
0xC00180B6
The reserved station parameter (Table 100, register 77) have
invalid values.
0xC00180B7
The setting for the behavior of PROFINET IO faults (stop
internal data bus) when using PROFIsafe modules is not allowed.
Additional
Description
value
0xC0018009
Module or fieldbus coupler is not configured.
H
. Additional fault information is available in
Appendix
207