Channel Specific Diagnostics; Channel Diagnostics; Table 165: General Structure "Channeldiagnosis" And „Extchanneldiagnosis; Table 166: "Channeldiagnosisdata" Instance Structure - WAGO 750-370 Manual

Profinet io fieldbus coupler 2-port; 100 mbit/s; digital and analog signals
Hide thumbs Also See for 750-370:
Table of Contents

Advertisement

WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
14.5.1

Channel Specific Diagnostics

Errors occurring when configuring and setting the parameters of the station
(IO device) and the connected I/O modules as well as external errors from the
connected periphery are reported by the fieldbus coupler via channel specific
diagnostics. External errors reported by the subassemblies (e.g. short circuits, line
interruptions) are only transmitted to the IO controller after release when setting
the module's parameters.
The "BlockType" in the structure head of the data set corresponds to the value for
the channel diagnostics (0x0010). The length defines the following diagnostics
data for faulty sub-modules or channels.
The data for the channel diagnosis is triggered using a general structure (see
ChannelDiagnosis or ExtChannelDiagnosis).
The respective fault details for the respective channels follow after this. The
general structure has a length of 10 bytes and is composed of as follows:
Pos : 98.2 /Serie 750 (WAGO-I/O-SYST EM)/Anhang/Kanalspezifisc he Diag nose 1.2 ( 750-370) @ 23\mod_1439468934326_21.doc x @ 188826 @ @ 1
Table 165: General Structure "ChannelDiagnosis" and „ExtChannelDiagnosis"
Byte
Data type
offset
0 / 1
WORD
2 / 3
WORD
4 / 5
WORD
BYTE
6 / 7
BYTE
8 / 9
WORD
Pos : 98.3 /Serie 750 (WAGO-I/O-SYST EM)/Anhang/Kanalspezifisc he Diag nose 1.3 ( 750-370) @ 23\mod_1439214887857_21.doc x @ 187780 @ 4 @ 1
14.5.1.1

Channel Diagnostics

The channel diagnostics is set by the fieldbus coupler when external channel
errors occur (e.g., short circuits or overvoltage). These error types are defined in
the PROFINET IO specification.
The error type (UserstructureIdentifier) contains the value for channel diagnostics
(0x8000).
Each error of a signal channel or sub-module is described in a data set (see
ChannelDiagnosisData).
The structure of the data set has 6 bytes and is composed of as follows:
Table 166: "
Byte
Data
offset
type
Manual
Version 2.0.0
0x00
0x01
0x80
0x00
0x08
0x00
ChannelDiagnosisData" Instance Structure
Description
Description
Slot-faulted module (SlotNumber)
Value
0 ... 128
range
Slot-faulted submodule (SubslotNumber)= 1
Diagnosis on submodule level (0x8000)
Specification = Error pending (0x08)
Constant (0x00)
Diagnostic structure (UserStructureIdentifier)
0x8000 Channel diagnostics
0x8002 Extended channel diagnostics