26
System Description
Pos : 18.15.13 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Beis piel: @ 3\mod_1232630417843_21.doc x @ 26605 @ @ 1
Example:
Pos : 18.15.14 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Beispi el 1 (Standar d) @ 3\mod_1232950106875_21.doc x @ 26792 @ @ 1
Calculating the current consumption on the fieldbus coupler:
Internal current consumption of the coupler
Total current for I/O modules
Sum I
(5 V) total
Pos : 18.15.15 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Inter ne Stromaufnahme/Summenstr om @ 3\mod_1232950111375_21.doc x @ 26816 @ @ 1
The internal current consumption is indicated in the technical data for each bus
terminal. In order to determine the total requirement, add together the values of all
I/O modules in the node.
Please note the aggregate current for I/O modules. It may be necessary to
supply potential!
When the sum of the internal current consumption for the I/O modules exceeds
their aggregate current, you must use a supply module with bus power supply.
Install it before the position where the permissible aggregate current would be
exceeded.
Pos : 18.15.16 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Beis piel: @ 3\mod_1232630417843_21.doc x @ 26605 @ @ 1
Example:
Pos : 18.15.17 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Beispi el 2 (Standar d) @ 3\mod_1232950109109_21.doc x @ 26804 @ @ 1
Calculating the total current on a standard fieldbus coupler/controller:
A node configuration with 20 relay modules (750-517) and 30 digital input
modules (750-405) should be attached to a fieldbus coupler/controller:
Internal current consumptions
Sum of internal current consumptions
However, the fieldbus coupler can only provide 1650 mA for the I/O modules.
Consequently, an internal system supply module (750-613), e. g. in the middle of
the node, should be added.
Pos : 18.15.18 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/Systemvers orgung - Ausl egung - Berec hnung Ei ngangsstrom @ 3\mod_1232950109984_21.doc x @ 26808 @ @ 1
Recommendation
Utilize the smartDESIGNER feature WAGO ProServe
fieldbus node assembly. You can test the configuration via the integrated
plausibility check.
The maximum input current of the 24 V system supply is 500 mA. The exact
electrical consumption (I

750-370 PROFINET IO Fieldbus Coupler

20 × 90 mA = 1800 mA at 5 V
+ 30 × 2 mA =
) can be determined with the following formulas:
(V)
WAGO-I/O-System 750
350 mA at 5 V
1650 mA at 5 V
2000 mA at 5 V
60 mA at 5 V
1860 mA at 5 V
®
software to configure
Manual
Version 2.0.0