Table 36: Legend For The Figure "Ipar Server; 750-370 Profinet Io Fieldbus Coupler - WAGO 750-370 Manual

Profinet io fieldbus coupler 2-port; 100 mbit/s; digital and analog signals
Hide thumbs Also See for 750-370:
Table of Contents

Advertisement

88
Function Description

Table 36: Legend for the Figure "iPar Server"

No. Explanation
1
Instantiation of the "iPar Server" function
2
CDP Tool Start and parameter transfer (e. g., node address)
3
Individual parameterization and start-up, test and release
4
Transfer of individual parameter backup (signature) to the host
5
During start-up, transfer of the signature to F-slave (Prm_Telegram)
6
Message to iPar server about diagnostic agent (alarm/status)
7
iPar server polls the diagnostic function block (Diag-FB) and starts "Save"
if required
8
iPar server polls the diagnostic function block (Diag-FB) and starts
"Restore" if required
The WAGO parameterization tool WAGO-SEDI is used for fail-safe
parameterization and can be executed from the configuration environment of the
IOCs used. To call up SEDI, three different communication paths are available
that correspond to the TCI conformance classes:
1
Local configuration interface (TCI CC1)
The SEDI is called up via WAGO-I/O-CHECK.
2
TCP/IP communication via WAGO service port 6626 (TCI CC2)
The SEDI is called up via WAGO-I/O-CHECK.
More Information on the TCI conformance classes!
More information on the TCI conformance classes is available in the quickstart
guide of the PROFINET IO fieldbus coupler. You can download the quickstart
guide free of charge from the WAGO Internet site at: www.wago.com.
More Information on the iPar server!
More information on the iPar server is available in the manuals for PROFIsafe
safety modules of the 750 and 753 series. You can download these manuals free
of charge from the WAGO Internet site at:
www.wago.com.
WAGO-I/O-System 750

750-370 PROFINET IO Fieldbus Coupler

Manual
Version 2.0.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents