Configuration Limits

7.5.1

Minimum Configuration

The minimum configuration is used when you only configure the station proxy
(DAP).
In this case, the application does not include any user data. The length of the
application data is zero.
The provider telegram contains the provider status of the submodules for
Interface, Port 1, Port 2 and station proxy (DAP). The provider telegram length is
64 bytes.
The consumer telegram contains the consumer status of the submodules for
Interface, Port 1, Port 2 and station proxy (DAP). The consumer telegram length
is also 64 bytes.
7.5.2

Maximum Configuration

Due to one of the following boundary conditions, you can achieve the maximum
configuration:
Maximum of 128 modules or submodules
Maximum input data length of 256 bytes configured
Maximum output data length of 256 bytes configured
Maximum provider data length of 320 bytes in the real time telegram
exhausted
Maximum consumer data length of 320 bytes in the real time telegram
exhausted