Fail-safe Module Parameters (F-Parameter)

Fail-safe I/O modules require the standardized PROFIsafe configuration to ensure
safe exchange of production data.

Table 45: Fail-safe Module Parameters (F-Parameters)

Parameter
F_Check_iPar
F_SIL
F_CRC_Length
F_Par_Version
F_Source_Add
F_Dest_Add
F_WD_Time
F_iPar_CRC
8.6.5

General Channel Parameters

Channel properties can be set individually for a number of I/O modules. The
following channel-specific settings can be made depending on the I/O module:
Setting
*1)
NoCheck
*1)
SIL3
*1)
3-Byte-CRC
*1)
1
1 ... 65534
1 ... 1023 (65534
*2)
150
50 ... 10000
*4)
*2)
0
... 4294967295
*1)
Fixed settings
*)
Default settings
*3)
For 75x-66x/000-003 F-Modules only by software
*4)
For 75x-66x/000-003 F-Modules only and to use the iPar server
750-370 PROFINET IO Fieldbus Coupler
Description
There are no individual parameters contained in the
F-parameters that have to be checked.
The module complies with safety category 3.
The transfer of production data transfer is
safeguarded using a 3-byte CRC in case of
PROFINET IO.
The version of the parameters set structure is 1.
The F-Source address addresses the F-Host.
*3)
) The F-Target address addresses the F-Device.
The F-Watchdog monitors the data exchange
between the F-Host and F-Device. The settings are
carried out in milliseconds.
Signature of the individual parameter set currently
used in the module required to use the iPar server.
WAGO-I/O-System 750
Manual
Version 2.0.0