Function Description
Pos : 66.13 /Serie 750 ( WAGO-I/O-SYST EM)/Funkti onsbesc hrei bung/F unktions besc hreibung 750-0370 - Teil 4 @ 23\mod_1438937324097_21.doc x @ 187618 @ 222 @ 1
7.7

Using Fail-Safe I/O Modules (PROFIsafe V2)

The fieldbus coupler allows you to operate all PROFIsafe V2 I/O modules of the
750 and 753 series.
You can activate diagnostics channel-by-channel using the fieldbus coupler. The
module diagnostics is implicitly for use of the iPar client message.
The submodules of the PROFIsafe V2 I/O modules allow storage of module-
specific parameters, i. e., safety-related parameters (individual parameter) on an
available iPar server of the higher-level control.
That is a significant advantage when a module has to be replaced. Initially, the I/O
module just installed has the default settings. The previously saved individual
parameterization is automatically set via the non-secure functionality of the
respective iPar server function block. This ensures that productive data exchange
can be included again immediately after the exchange.
More Information on the PROFIsafe V2 I/O modules!
More information on the PROFIsafe V2 I/O modules is available in the respective
manuals of the PROFIsafe safety modules of the 750 and 753 series. You can
download these manuals free of charge from the WAGO Internet site at:
www.wago.com.