Table 170: Fault Cases of Analog Output Modules with Diagnostics Capability

Item
number
75x-553,
75x-555,
75x-557,
75x-559,
75x-560
75x-562,
75x-563
Manual
Version 2.0.0
Data
Error type
format
WORD
0x0009 / 9
WORD
0x0001 / 1
0x0002 / 2
0x0005 / 5
0x0007 / 7
0x0008 / 8
0x0011 / 17
Explanation
Error
Output short circuit
Internal error (e. g. hardware error)
Short circuit
Output short circuit
Undervoltage
24V field power below 20V
Overtemperature
Permissible temperature of output driver
exceeded
Upper limit value
Configured limit value exceeded
exceeded
Lower limit value
Configured limit value undershot
undershot
Sensor or load
Field voltage too low
voltage missing