WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
The entries for the incorrectly configured modules/submodules then follow. The
number of existing entries is stored in the preliminary structure of the
"ModuleDiffBlock".
Table 179: Structure of the Odd Modules within the Configuration
Byte
Data type
offset
0 / 1
WORD
2 / 3
DWORD
4 / 5
6 / 7
WORD
8 / 9
WORD
Manual
Version 2.0.0
Description
Slot with odd module
Range
1 ... 255
Identification of the physically plugged module
("ModuleIdentNumber")
Module state
0x0000 Module not plugged
0x0001 ModuleIndentNumber wrong
0x0002 Module is okay, but at least one submodule is
locked, worng or missing
0x0003 Module is not the same as requested – but the
IO device was able to adapt by its own
knowledge
0x0004
...
Reserved
0xFFFF
Number of submodule slots with odd submodules,
otherwise 0
Appendix
211