98
Commissioning
8.6.1.6
Response to K-Bus Failure
Table 43: Parameterization DAP – Attribute Response to K-Bus Failure
Attribute Name
Response to K-Bus
failure
8.6.2
Parameterization of the I/O-Modules
The configurable attributes for the various I/O module types are listed in the
appendix.
More information on the I/O module parameters!
The individual attribute values and descriptions are available in the appendix in
the respective subsections under the section "Parameters for the I/O Modules".
Pos : 69.6 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Attribute Value
Description
Failures in the internal communication of the
fieldbus coupler and bus terminals, e. g. missing
end terminal
PROFINET IO
•
communication is
*)
stopped
input image is
•
cleared
•
input image is stored
*)
Default settings
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
separating the cyclic connection to the
PROFINET IO controller.
all input informations of the respective
peripheral modules are set to zero.
the input information of the peripheral
modules immediately before the fault is
maintained.
Manual
Version 2.0.0