10.3

PROFINET IO Diagnostics

PROFINET IO allows exact diagnostics of the type and source of an occurring
error by reading the record data sets for the diagnostics.
The respective configuration software / IO supervisor is normally used, which
provides graphical processing of the diagnostic data (e.g. STEP 7, etc.).
In addition to the record data sets for module/submodule parameterization, a
number of record data sets are available for acyclic communication for
diagnostics (listed in the following section).
The structure of the standardized diagnostic data sets and channel-specific
diagnostics are then explained.
Standard and manufacturer-specific diagnostic data sets are mapped according to
the extended channel diagnostics.
10.3.1

Diagnosis Data Sets

The diagnostic information of the fieldbus coupler (IO device) can be read
acyclically using standard diagnosis data sets (records). The structure of the data
sets is defined in the PROFINET IO specification.
More details are available in the specification under "IODReadReq" or
"IODReadRes".
The data set number (index) makes it possible to distinguish between the
diagnostics level (device, module, submodule or channel error) and the
diagnostics structures.
The list of diagnosis data sets listed below provides the respective message
structures in the case of pending diagnostics.
Pos : 78 /Serie 750 ( WAGO-I/O-SYST EM)/Di agnose/Fel dbus koppl er/-contr oller/PROF INET-Di agnose/PR OFIN ET IO-Diagnos e - T eil 2 (370) @ 23\mod_1435733764818_21.doc x @ 185034 @ @ 1

Table 64: Retrievable Record Data Sets for Diagnostics

Data set number
(index)
0x800A
0x800B
0x800C
0xC00A
0xC00B
0xC00C
0xE002
0xE00A
0xE00B
0xE00C
0xF00A
0xF00B
0xF00C
Pos : 79 /Serie 750 ( WAGO-I/O-SYST EM)/Di agnose/Fel dbus koppl er/-contr oller/PROF INET-Di agnose/PR OFIN ET IO-Diagnos e - T eil 3 @ 16\mod_1374154214827_21.doc x @ 126566 @ 3 @ 1
Manual
Version 2.0.0
Description
32778
Standardized channel diagnostics of a submodule slot
32779
(subslot specific)
32780
49162
Channel diagnostics of a slot (slot specific); currently
49163
identical with the data set number 800A, as only one
submodule can exist for each module.
49164
Deviations in the specified and actual configuration of the
57346
submodules assigned to the IO controller (IOAR).
57354
Channel diagnostics of all signal channels allocated to a
57355
connection (AR), contains all channel diagnostics structures
of the submodule slots.
57356
61450
Channel diagnostics of all signal channels allocated to the
61451
application profile 0 (API 0), contains all channel
diagnostics structures of the individual submodule slots.
61452
Diagnostics
127
Available on
slot
0 ... 128
0 ... 128
0
0
0