166
Appendix
14.1.6.4

Serial Interfaces

The group of serial interfaces is divided into two module types.
Table 85: Module Types – Serial Interfaces
Module type
1SER
Module type
DXCH
For the serial interfaces, the provider and consumer status (IOPS, IOCS) of the
input or output information are exchanged between the IO controller and IO
device in both directions.
The group of serial interfaces is divided into the following submodule types.
Table 86: Submodule Types and Data Lengths – Serial Interfaces
PNIO module type
PNIO submodule type
1SER
Ser. Interface 5 byte
Ser. Interface 8 byte
Ser. Interface 24 byte
Ser. Interface 48 byte
DXCH
DXCH (4 byte I/O)
DXCH (6 byte I/O)
Description
Serial Interfaces
Description
Data Exchance Modules
Data type
{Unsigned8,
Unsigned8[5]}
{Unsigned8,
Unsigned8,
Unsigned8[6]}
{Unsigned8,
Unsigned8,
Unsigned8[22]}
{Unsigned8,
Unsigned8,
Unsigned8[46]}
{Unsigned8,
Unsigned8[3]}
{Unsigned8,
Unsigned8[5]}
750-370 PROFINET IO Fieldbus Coupler
Substitute I/O modules
75x-650, 75x-651, 75x-653,
75x-652,
plus all variations
Substitute I/O modules
75x-654
Process data length [byte]
Input (I-PI) Output (O-PI)
6
6
8
8
24
24
48
48
4
4
6
6
WAGO-I/O-System 750
Telegram
allocation [byte]
Input
Output
8
8
10
10
26
26
50
50
6
6
8
8