All Profibus Dp And Profinet Io Fieldbus Couplers/Controllers; Table 47: Specific Module/Channel Parameters For 75X-461/003-000 - WAGO 750 Series Manual

4ai u/i diff galv 4-channel analog input; for voltage/current
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv
10.1.2.1

All PROFIBUS DP and PROFINET IO Fieldbus Couplers/Controllers

The following assignment applies to the parameters of the I/O module when
using PROFIBUS DP and PROFINET IO fieldbus devices.

Table 47: Specific Module/Channel parameters for 75x-461/003-000

GSD file
Parameter
Number format
Siemens
S5 format
Input filter frequency
Signal type Channel x
(x = 0...3)
Input filter
Channel x
(x = 0...3)
User scaling
Offset
Gain
)
*
Default setting
)
**
The resolution 1/16384 is already taken into account in WAGO-I/O-CHECK.
Value
)
Twos Complement*
Sign magnitude
)
disabled*
activated
)
50 Hz*
60 Hz
disabled
0 - 10 V
+/ − 10 V
0 - 20 mA
)
4 - 20 mA*
3,6 - 21,0 mA
(Namur NE43)
+/− 20 mA
+/− 200 mV
)
disabled*
activated
)
disabled*
activated
)
− 32768 ... 0*
... 32767
)
− 32768 ... 16384*
...
32767
WAGO-I/O-CHECK
Checkbox
Value
Number format
Twos Complement*
Sign magnitude
Siemens
Off*
S5 format
On
Input filter frequency
50 Hz*
60 Hz
Signal type
Channel disabled
0 - 10 V
+/ − 10 V
0 - 20 mA
4 - 20 mA*
3,6 - 21,0 mA
(Namur NE43)
+/− 20 mA
+/− 200 mV
Input filter
Off*
On
Checkbox disabled*
User scaling
Checkbox activated
− 32768 ... 0*
Offset
32767
− 2.0000 ... 1.0000*
Gain
1.9999
Appendix