Table 175: Additional Error Information Fault Type "Internal Bus Fault 0x100"

Fault type "Internal bus fault (0x0100)"
Extended
fault type
0x0001
0x0003
0x0003
0x0003
0x0003
0x0003
0x0004
0x0005
Invalid module configurations are reported via manufacturer specific fault of type
101
. Additional fault information is available in the following table.
H
Table 176: Additional Error Information Fault Type "Configuration fault (0x0101)"
Fault type "Configuration fault (0x0101)"
Extended
fault type
0x0012
0x0013
0x0015
0x0016
0x0017
0x0022
0x0023
0x0025
0x0026
0x0027
If a fault occurs on the internal data bus system when the PNIO connection is
being established and if auto reset of the internal data bus was set by the station
proxy, then the PNIO connection must be interrupted and re-established in order
to set the parameters of the connected I/O modules. The reconfiguration request is
triggered by a manufacturer specific fault of type 102
information is available in the following table.
Additional
Description
value
0x00000106
The module configuration that has been determined on the
internal bus after AUTORESET differs from the configuration
performed before the internal bus fault occurred.
0x01100300
Internal bus protocol fault due to internal bus RESET fault.
0x01110300
Internal bus protocol fault due to command fault.
0x01120300
Internal bus protocol fault due to faulty input data.
0x01140300
Internal bus protocol fault due to faulty output data.
0x01180300
Internal bus protocol fault caused by timeout.
0x011204xx
Internal bus interruption after module slot xx (xx = 0 ... 128).
0x011005xx
Internal bus initializing fault because of an abortive register
communication with the module on slot xx (xx = 1 ... 128).
Additional
Description
value
0xC0018012
The bit offset for the inputs of the module is not allowed.
0xC0018013
The bit offset for the inputs of the module exceed the maximum
offset.
0xC0018015
The configured data length for the input module is smaller than
expected.
0xC0018016
The configured data length for the input module is larger than
expected.
0xC0018017
The configured data length for the input module is not allowed.
0xC0018022
The bit offset for the output of the module is not allowed.
0xC0018023
The bit offset for the output of the module exceeds the maximum
offset.
0xC0018025
The configured data length for the output module is smaller than
expected.
0xC0018026
The configured data length for the output module is larger than
expected.
0xC0018027
The configured data length for the output module is not allowed.
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
. Additional fault
H
Manual
Version 2.0.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents