Evaluating The Node Status; Table 54: Node Status Diagnostics - Solution In Event Of Error - WAGO 750-370 Manual

Profinet io fieldbus coupler 2-port; 100 mbit/s; digital and analog signals
Hide thumbs Also See for 750-370:
Table of Contents

Advertisement

118
Diagnostics
Pos : 75.10 /Serie 750 ( WAGO-I/O-SYST EM)/Diagnos e/F eldbus koppler/-c ontroll er/PR OFIN ET-Diag nos e/Knotenstatus aus werten - I/O- LED (PROF INET IO-Koppler) ( 750-370) @ 23\mod_1439208907733_21.doc x @ 187722 @ 3 @ 1
10.1.2

Evaluating the Node Status

The I/O LED indicates the operating status of communication between the
fieldbus coupler and I/O modules.
Table 54: Node Status Diagnostics – Solution in Event of Error
LED Status
I/O
green
orange
flashing
red
permanent
red
flashing
red
cyclical
flashing
OFF
After switching on the power supply, the boot loader copies the device firmware
to the working memory, the I/O LED flashes orange.
The device firmware then starts and initializes the internal data bus. This is
indicated by red flashing at 10 Hz for 1-2 seconds.
After starting up without any errors, the I/O LED lights up green.
In the event of error, the I/O LED flashes red.
The flash codes are used to indicate detailed error messages. An error is indicated
by up to 3 cyclical flash sequences.
After eliminating the error, restart the fieldbus node by switching the fieldbus
coupler power supply off and on again.
Explanation
Data cycle on the internal data bus.
The boot loader is copying the device
firmware from the flash memory to the
working memory of the fieldbus
coupler.
Fieldbus coupler has a hardware defect.
Flashing at approx. 10 Hz points to
initialization of the internal data bus or
to a general internal data bus error.
Up to three successive blinking
sequences indicate internal data bus
errors. There are short intervals between
the sequences.
No data cycle on the internal data bus.
WAGO-I/O-System 750
750-370 PROFINET IO Fieldbus Coupler
Solution
Normal operating conditions.
-
Replace the fieldbus coupler.
Note the following blinking sequence.
Evaluate the blinking sequences based
on the following blink code table. The
blinking indicates an error message
comprised of an error code and error
argument.
The fieldbus coupler supply is off.
Manual
Version 2.0.0

Hide quick links:

Advertisement

Table of Contents
loading