Pos : 18.15.28 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Leg ende z u Abbildung "F el dvers orgung für Standard-F eldbus k/F el dvers orgung - Legende zu Abbil dung "F eldversorgung für Standard-Fel dbus k/-contr oller u er w EC O-F" @ 16\mod_1375693993330_21.doc x @ 127730 @ @ 1
Table 6: Legend for Figure "Field Supply for Standard Couplers/Controllers and Extended ECO
Couplers"
Field supply
1
24 V (-15 % / +20 %)
2
0 V
3
Optional ground potential
Power jumper contacts
4
Potential distribution to adjacent I/O modules
Pos : 18.15.29 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss - Weiterl eitung Vers orgungsspg., Strombel astung 10 A, neue Eins peisekl emme @ 8\mod_1279805441785_21.doc x @ 60845 @ @ 1
The field-side power supply is automatically derived from the power jumper
contacts when snapping an I/O module.
The current load of the power contacts must not exceed 10 A on a continual basis.
By inserting an additional power supply module, the field supply via the power
contacts is disrupted. From there a new power supply occurs which may also
contain a new voltage potential.
Pos : 18.15.30 /Seri e 750 ( WAGO-I/O-SYSTEM)/Systembes chr eibung/Versorgung/F eldversorgung - Ans chl uss - 2 Hi nweise: Potential neu ei ns peis en + Dis tanz kl emme @ 3\mod_1232950091343_21.doc x @ 26724 @ @ 1
Re-establish the ground connection when the connection to the power jumper
contacts is disrupted!
Some I/O modules have no or very few power contacts (depending on the I/O
function). Due to this, the passing through of the relevant potential is disrupted. If
you require a field supply via power jumper contacts for subsequent I/O modules,
then you have to use a power supply module.
Note the data sheets of the I/O modules.
Use a spacer module when setting up a node with different potentials!
In the case of a node setup with different potentials, e.g. the alteration from
DC 24 V to AC 230 V, you should use a spacer module. The optical separation of
the potentials acts as a warning to heed caution in the case of wiring and
maintenance works. Thus, you can prevent the results of wiring errors.
Pos : 18.15.31 /D okumentation allgemein/Gliederungselemente/---Sei tenwechsel--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 2.0.0
System Description
29